The largest LPG Equipment Supplier &

Manufacturer in Sub-Saharan Africa

Adceng

 

Rego Rotogages

2070 Series

¾" Rotogages® for Small Stationary and Mobile LP-Gas Containers.

Rotogages® are designed to provide accurate determination of LP-Gas container contents. They may be end or side mounted in a standard ¾" NPT coupling on stationary or mobile containers. To guarantee accurate measurement, they should not be used on stationary containers that exceed 60" I.D. or on mobile containers, subject to vibration, with an I.D. of more than 24".

Features

  • Provides long, trouble-free performance and ease of operation.
  • Polished stems assure bind-proof operation.
  • Dial face is dual calibrated to provide greater accuracy in reading contents in containers which are not level.

Materials

Body Brass
Stem Brass Tubing
Dip Tube Seamless Brass Tubing
Dial Plate Aluminum
Indicator Malleable Iron

Ordering Information

NOTE: The dip tube must be cut to the required length (½ of container inside diameter minus ½"), when mounted on center line of tank.

9091RM and 9092RM Series

For Small Mobile or Stationary Containers.

Ordering Information

* Supported Design
NOTE: The dip tube must be cut to the required length (½" of container inside diameter minus 5½").

9090 and AA9090 Series

1" Rotogages® for Large Mobile and Stationary Containers.

Rotogages® are designed to provide an accurate determination of LPGas or anhydrous ammonia container contents. They mount in a standard 1" NPT coupling on large mobile or stationary containers. To operate the Rotogages®, the vent valve is opened and the dip tube rotated slowly from the container vapor space to the liquid space. The difference in appearance of the discharge indicates when the liquid level is reached. Dial readings then indicate the percentage of product in the container.

Features

  • Supported design (TS Models) eliminates whipping and the need for internal support hangers.
  • Resistance-free nylon bearing inserts reduce friction and promote operating ease.
  • Dial face is dual calibrated to provide greater accuracy in reading contents in containers which are not level.
  • Interchangeable accessory dials permit interchange-able service between LP-Gas and anhydrous ammonia.

Materials

Body Steel
Stem Steel
Dip Tube Seamless Steel
Indicator Malleable Iron
Dial Plate Aluminum
Vent Stem Stainless Steel

Rotogage® Dials

* Dial permits higher filling level, as per NFPA 58, (1983) Par. 4-5.2.1, Table 4-5.2.1

Previous  Home  Top